YR40.241 Datasheet by PULS, LP

PULS DIMENSION M R M G D | s T- D o N | M IE EE U ”@”s ”5"" ca Sg-IEME B“ [Is UL 503 \EC 60950-1 UL 609504 D N V' G L GE <9 classl="" div="" 2="" atex="" dnvgl.com/af="" marine="">
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
1/19
M
OSFET
R
EDUNDANCY
M
ODULE
For N+1 and 1+1 Redundant Systems
Dual Input with Single Output
Suitable for all Power Supplies
Only 72mV Voltage Drop at 20A Output Current
Only 2.15W Loss at 20A and 6.3W at 40A Output Current
160% (65A) Peak Load Capability
Reverse Input Polarity Protection
Full Power Between -40°C and +70°C
Width only 36mm
Rugged Metal Housing
Easy Wiring:
Distribution Terminal for Negative Pole Included
3 Year Warranty
GENERAL DESCRIPTION
The YR40.241 is a redundancy module, which can be
used to build 1+1 and N+1 redundant system. It is
equipped with two input channels, which can be
connected to power supplies with up to 20A output
current and one output, which can carry nominal
currents up to 40A. The module is suitable for power
supplies with constant current overload behavior as well
as any kind of “Hiccup” overload behavior. In addition
to the YR40.241, the YR40.242 is also available which is
cost-optimized and suitable for all DIMENSION power
supplies except the QT20 and QTD20 series.
The novelty of this redundancy module is the utilization
of mosfets instead of diodes for the decoupling of the
two input channels. This reduces the heat generation
and the voltage drop between input and output. The
redundancy module does not require an additional
auxiliary voltage and is self-sufficient even in case of a
short circuit across the output.
Due to the low power losses, the unit is very slender and
only requires 36mm width on the DIN-rail. Large
connection terminals allow for a safe and fast
installation with a large international approval package.
This unit is suitable for nearly every application.
SHORT-FORM DATA
Input
voltage DC 12-28V
±
30%
Input voltage
range
Input current
continuous
for 5 seconds
Output current
continuous
40-65A
for 5
seconds
at cont. overload
or short circuit
Input to output
voltage drop
typ. 112mV
typ. 140mV
input: 2x10A
input: 1x20A
input: 2x20A
Power losses
at no load
input: 2x10A
input: 1x20A
input: 2x20A
Temperature range
operational,
no de
-rating req.
Dimensions
36x124x127mm*)
WxHxD
*) plus 4mm in depth for the screw terminal
ORDER NUMBERS
Redundancy YR40.241 12-28V Standard unit
Module
Accessory ZM2.WALL Wall/ panel mount
bracket
ZM11.SIDE Side mount bracket
MARKINGS
UL 508
IEC 60950-1
UL 60950-1
Class I Div 2
ATEX
Marine
PULS I DIMENSION
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
2/19
INDEX
Page Page
1. Intended Use .......................................................3
2. Installation Instructions ......................................3
3. Input and Output Characteristics .......................5
4. Power Losses ........................................................6
5. Lifetime Expectancy and MTBF ...........................7
6. Terminals and Wiring ..........................................8
7. Functional Diagram .............................................9
8. Front Side and User Elements .............................9
9. EMC .................................................................... 10
10. Environment ...................................................... 11
11. Protection Features ........................................... 12
12. Safety Features .................................................. 12
13. Dielectric Strength ............................................ 12
14. Approvals and Fulfilled Standard .................... 13
15. Regulatory Compliance .................................... 14
16. Physical Dimensions and Weight ..................... 15
17. Accessories ........................................................ 16
18. Application Notes ............................................. 17
18.1. Recommendations for Redundancy ......... 17
18.2. Inductive and Capacitive Loads................ 17
18.3. Sidewards Installation Clearances............ 17
18.4. 1+1 Redundancy up to 20A ...................... 18
18.5. N+1 Redundancy, Example with 60A ...... 18
18.6. Mounting Orientations ............................ 19
The information presented in this document is believed to be accurate and reliable and may change without notice.
No part of this document may be reproduced or utilized in any form without permission in writing from the publisher.
TERMINOLOGY AND ABREVIATIONS
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
Earth, Ground This document uses the term earthwhich is the same as the U.S. term ground”.
T.b.d. To be defined, value or description will follow later.
DC 24V A figure displayed with the AC or DC before the value represents a nominal voltage with
standard tolerances (usually ±15%) included.
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
24Vdc A figure with the unit (Vdc) at the end is a momentary figure without any additional
tolerances included.
may A key word indicate flexibility of choice with no implied preference
shall A key word indicate a mandatory requirement
should A key word indicate flexibility of choice with a strongly preferred implementation
1+1 Redundancy Use of two identical power supplies in parallel to provide continued operation following most
failures in a single power supply. The two power supply outputs should be isolated from each
other by utilizing diodes or other switching arrangements. E.g. two 10A power supplies are
needed to achieve a 10A redundant
system.
N+1 Redundancy Use of three or more identical power
supplies in parallel to provide
continued operation following most
failures in a single power supply. All
power supply outputs should be
isolated from each other by utilizing
diodes or other switching
arrangements.
E.g.: To achieve a 40A redundant
system, five 10A power supplies are
needed in a N+1 redundant system.
N+1
Redundancy
1+1
Redundancy
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
IN 1
OUT
IN 2 IN 1
OUT
IN 2 IN 1
OUT
IN 2
Load
+
-
AC
DC
AC
DC
Load
+
-
IN 1
OUT
IN 2
PULS I DIMENSION 1.| U 2.| |
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
3/19
1. I
NTENDED
U
SE
This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control,
process control, monitoring and measurement equipment or the like. Do not use this device in equipment where
malfunction may cause severe personal injury or threaten human life.
The redundancy module can be used with any type of power supply as long as the maximum output current ratings
are not exceeded. It is suitable for power supplies with continuous overload current as well as any kind of intermittent
(Hiccup) overload behavior
2. I
NSTALLATION
I
NSTRUCTIONS
WARNING
Risk of electrical shock, fire, personal injury or death.
- Turn power off before working on the device and protect against inadvertent re-powering.
- Do not open, modify or repair the device.
- Use caution to prevent any foreign objects from entering into the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on, and immediately after power-off. Hot surface may cause burns.
Obey the following installation instructions:
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to
the factory for inspection.
Install the device in an enclosure providing protection against electrical, mechanical and fire hazards.
Do not ground or earth the positive output pole which could prevent redundancy in case of a ground failure. Ground
the negative output pole, when needed.
Use only power supplies with a negligible output ripple voltage in the low frequency range between 50Hz and 10kHz
when used in marine applications according to the GL regulations.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the top of the device. Other
mounting orientations require a reduction in output current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper cables that are
designed for a minimum operating temperature of 60°C for ambient temperatures up to +45°C, 75°C for ambient
temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. Ensure that all strands of a stranded wire
enter the terminal connection.
Unused screw terminals should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or frost is allowed.
The enclosure of the device provides a degree of protection of IP20.
The input must be powered from a PELV or SELV source or an “Isolated Secondary Circuit” in order to maintain a SELV
or PELV output.
Check correct input polarity. The device will not operate when input voltage is reversed.
The device is designed as “Class of Protection III” equipment according to IEC 61140.
A PE (ground) connection is not required. However, connecting the chassis ground terminal to ground can be
beneficial to gain a high EMI immunity.
The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not
cover ventilation grid!
The device is designed for altitudes up to 6000m (19685ft). See additional requirements in the product datasheet for
use above 2000m (6560ft).
IIIIIIIII
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
4/19
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side.
Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device is permanently loaded with
less than 50%, the 5mm can be reduced to zero. Under special circumstances clearances can be reduced. See details in
the product datasheet.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the ambient
or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity. I
Installation Instructions for Hazardous Location Areas
The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II Category 3 (Zone 2)
environments.
Hazardous Location classification: ATEX: EPS 11 ATEX 1 312 X, II 3G EX ec IIC T4 Gc
WARNING EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the device unless power has
been switched off or the area is known to be non-hazardous.
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the
requirements of the EN 60079-0.
é} £3761" TC 1 V , p , , a , + , P , , 1 , DIMENSION PULS
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
5/19
3. I
NPUT AND
O
UTPUT
C
HARACTERISTICS
Number of inputs
2
Number of outputs
1
Input voltage
nom.
DC
12-28V ±30% The input circuitry must meet the SELV requirements
stipulated by IEC/EN/UL 60950-1.
Input voltage range
8.4-36.4Vdc
Voltage
drop, input to output typ. 140mV at 2x20A, see Fig. 3-1
typ. 72mV at 2x10A, see Fig. 3-1
typ. 112mV at 1x20A, see Fig. 3-2
I
nput current nom. 2x 0-20A continuous
nom. 2x 20-32.5A for 5 seconds
max
2x 32.5A
at continuous overload or short circuit
Peak input current
max. 1000A for max. 1ms per input
Ou
tput current nom. 40A continuous
nom.
40-65A
for 5 seconds
max. 65A at continuous overload or short circuit
Reverse current
max. 1mA at 24V, per input, -40°C to +70°C
Reverse voltage
max. 40Vdc voltage applied to the output, continuously allowed
Out
put capacitance typ. 320µF
Note: Ensure that the continuous output current does not exceed 65A. Check the short-circuit current of the power sources and if the
power source can deliver more than 65A together, use an appropriate fuse on the output.
Fig. 3-1 Input to output voltage drop when both inputs draw current
(typical 1+1 redundant case, when the output voltages of the two units are equal)
Voltage Drop, typ
0mV
10A 30A
20mV
40mV
60mV
80mV
100mV
120mV
40A20A
Output:
A... 25°C
B... 60°C
2x10A2x5A
Input / Output Current
Input:
2x20A2x15A
0
0
140mV
160mV
AB
V
A
QS/QT20
24V,20A
+
-
QS/QT20
24V,20A
+
-
V
A
I
1
I
2
U
1
U
2
I
1
I
2
=U
2
U
1
=Voltage Drop U
1
=U
OUT
-
Output
A
V
I
OUT
U
OUT
Variable
Load,
0-40A
YR40
Input 1
Input 2
Output
Fig. 3-2 Input to output voltage drop when only one input draws current
Voltage Drop, typ.
0mV
5A 15A
20mV
40mV
60mV
80mV
100mV
120mV
20A
10A
A... 25°C
B... 60°C
Output Current
0
140mV
160mV
AB
Voltage Drop U
1
=U
OUT
-
Not used or
power supply
with lower
voltage
V
A
QS/QT20
24V,20A
+
-
I
1
U
1
Output
A
V
I
OUT
U
OUT
Variable
Load,
0-20A
YR40
Input 1
Input 2
Output
PULS DIMENSION 4.P <5?! if}?!="">
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
6/19
4. P
OWER
L
OSSES
DC 24V
Power losses
typ.
2.15W
input: 2x10A
typ. 6.3W input: 2x20A
typ. 2.6W input: 1x20A,
(only one input is connected to input voltage)
Standby power l
osses typ. 0.35W at no output current,
(only one input is connected to input voltage)
typ. 0.7W at no output current,
(both inputs are connected to input voltages)
Fig. 4-1 Power losses when both inputs draw equal current
Power Losses, typ.
0
0 5 10 30
1.0
2.0
4.0
5.0
7W
40A25
15 20 35
Output Current
A
3.0
A... 25°C
B... 60°C
6.0
B
Output
V
A
QS/QT20
24V,20A
+
-
e.g.
24.5V
V
A
I
1
I
2
U
1
U
2
A
V
I
OUT
U
OUT
I
1
I
2
=U
2
U
1
=Losses U
1
=U
OUT
-
*I
1
+ )( *
U
2
*I
2
I
OUT
QS/QT20
24V,20A
+
-
e.g.
24.5V
Variable
Load,
0-40A
YR40
Input 1
Input 2
Output
Fig. 4-2 Power losses when only one input is used
Power Losses, typ.
0
0 2.5 5 15
0.5
1.0
2.0
2.5
4W
20A12.57.5 10 17.5
Output Current
1.5
3.0
3.5
A... 25°C
B... 60°C
AB
Losses U
1
=U
OUT
-
*I
1
*I
OUT
Output
V
A
QS/QT20
24V,20A
+
-
I
1
U
1
A
V
I
OUT
U
OUT
YR40
Input 1
Input 2
Output
Variable
Load,
0-20A
Note: As soon as voltage is applied on input 2, an additional 0.35W will be consumed. It is not relevant, whether this channel contributes
to the output current or not.
PULS I DIMENSION 5. L E MTBF
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
7/19
5. L
IFETIME
E
XPECTANCY AND
MTBF
The redundancy module has two input channels which are completely independent from each other. Each control
circuit, auxiliary voltage source, or other circuitry in the module are designed separately for each input. The dual input
redundancy module can be considered as two single redundancy modules combined together in one housing. The only
common point is the circuit trace that ties the two separate circuits together at the output.
The MTBF figures below are for the entire dual input module. If the MTBF number of only one path is needed, simply
double the value from the table.
Input / output current
conditions
Input: 2x10A
Output: 20A
Input: 2x20A
Output: 40A
Lifetime expe
ctancy*) 649 000h *) 246 000h *) at 24V and 40°C
1 835 000h *) 696 000h *) at 24V and 25°C
MTB
F**) SN 29500, IEC 61709 3 386 000h 2 706 000h at 24V 40°C
5 667 000h 4 686 000h at 24V 25°C
MTBF
**) MIL HDBK 217F 116 000h 97 000h Ground Fixed GF40 (24V and 40°C)
155 000h 128 000h Ground Fixed GF25 (24V and 25°C)
612 000h 522 000h Ground Benign GB40 (24V and 40°C)
813 000h 687 000h Ground Benign GB25 (24V and 25°C)
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
8/19
6. T
ERMINALS AND
W
IRING
Input Output
Type
Screw termination
IP20 Finger safe construction.
Suitable for field installation.
Screw termination
IP20 Finger safe construction.
Suitable for field installation.
Solid wire
0.5-6mm2 0.5-16mm2
Stranded wire
0.5-4mm2 0.5-10mm2
American Wire Gauge
20-10 AWG 22-8 AWG
Ma
x. wire diameter 2.8mm (including ferrule) 5.2mm (including ferrule)
Wire stripping length
7mm / 0.275inch
12mm / 0.5inch
Screwdriver
3.5mm slotted or Pozidrive No 2 3.5mm slotted or Pozidrive No 2
Recommended tightening torque
0.8Nm, 7lb.in 1.2Nm, 10.6lb.in
To
connect the chassis to ground, use a ring-type terminal (ring cable lug) which is suitable for a M4 screw and connect
it to the chassis ground terminal on
top of the unit.
Instructions:
a)
The external circuitry of all terminals must meet the safety requirements stipulated by IEC/EN/UL 60950-1: SELV.
b)
Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum.
c)
Follow national installation codes and installation regulations!
d)
Ensure that all strands of a stranded wire enter the terminal connection!
e
) Screws of unused terminal compartments should be securely tightened.
f
) Ferrules are allowed.
g
) Do not connect or disconnect the wires from the terminals below -25°C (-13°F).
PULS DIMENSION 7.F D r ——————————— 1‘ 1 Q 1 III I I: W 1 1 W1 1 ‘ 111 D4”, I I 8F 5 U E O e so A mm,- 5 Q Q PULS DIMENSION % mum Redundancy Module
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
9/19
7. F
UNCTIONAL
D
IAGRAM
Fig. 7-1 Functional diagram
+
-
+
-
+
-
Input 1
control
control
Input 2
Chassis
Ground
Output
8. F
RONT
S
IDE AND
U
SER
E
LEMENTS
Fig. 8-1 Front side
A Output Terminals (screw terminals)
B Chassis Ground Terminals
To be connected on the top side of the housing with a ring-type terminal
(ring cable lug) which is suitable for a M4 screw.
Connection of the chassis is optional and not required since the unit fulfils
the requirements according to protection class III.
C Input Terminals for Input 1 (screw terminals)
D Input Terminals for Input 2 (screw terminals)
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
10/19
9. EMC
The redundancy module is suitable for applications in industrial environment as well as in residential, commercial and
light industry environment without any restrictions. A detailed EMC report is available on request.
Criterions:
A: Redundancy module shows normal operation behavior within the defined limits.
Notes:
*) A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic fields, e.g. hall
elements, electrodynamic microphones, etc.
EMC Emission
According generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
limits for DC power ports according
EN 61000-6-3 fulfilled *)
Radiated emission
EN 55011, EN 55032 Class B
This device complies with FCC Part 15 rules.
Operation is subjec
ted to following two conditions: (1) this device may not cause harmful interference, and (2) this
de
vice must accept any interference received, including interference that may cause undesired operation.
*) For information only, not mandatory for EN 61000-6-3. Provided, that power sources connected on the inputs fulfill the requirements too.
Switchi
ng frequency The internal auxiliary supply is generated with a boost converter.
The switching frequency is typ. 16kHz.
EMC Immunity
According generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic di
scharge EN 61000-4-2 Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A
Fast tra
nsients (Burst) EN 61000-4-4
Input lines
Output lines
2kV
2kV
Criterion A
Criterion A
Sur
ge voltage on input
lines
EN 61000-4-5 + -
+/- Chassis ground
500V
1kV
Criterion A
Criterion A
Surge voltage on output
lines
EN 61000-4-5 + -
+/- Chassis ground
500V
1kV
Criterion A
Criterion A
Conducted disturbance
EN 61000-4-6 0.15-80MHz 20V Criterion A
Power
-frequency magnetic
field *)
EN 61000-4-8 50Hz 30A/m Criterion A
PULS DIMENSION 10. E 7 7 7 7 7 \\L\ \FL\ 7 7fi 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 e 7 7 7 ‘LJ +\T\T 7 a 7 7 7 7m 7 7 7 7 a 7 7 7 m 7 7 7 o 7 7 ‘J‘n ‘41 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 _ _ _ 7 7 _
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
11/19
10. E
NVIRONMENT
Operational temperatur
e *) -40°C to +70°C (-40°F to 158°F)
Storage temperature
-40 to +85°C (-40°F to 185°F) for storage and transportation
Humidity
**) 5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal
***) 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Sh
ock ***) 30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude
0 to 2000m (0 to 6 560ft) without any restrictions
2000 to 6000m (6 560 to 20 000ft) reduce output power or ambient temperature,
see Fig. 10-2
Altitude de
-rating 2.5A/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 10-2
Over
-voltage category not applicable The concept of the overvoltage category is
used for equipment energized directly from
the low voltage mains (IEC 60664-1 §4.3.3.2.1).
Degree of poll
ution 2 IEC 62103, EN 50178, not conductive
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize while condensation is present
***) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard mounting
orientation.
Fig. 10-1 Output current vs. ambient temp. Fig. 10-2 Output current vs. altitude
Allowed Output Current
0
-40 0 20 40 7C
10
20
30
40
50
65A
60
-25
normal mode
at overload / short circuit
Ambient Temperature
Allowed Output Current
0
0 2000 4000 6000m
10
20
30
40
50
65A
normal mode
Altitude
overload / short circuit
A... Tamb < 70°C
B... Tamb < 60°C
C... Tamb < 50°C
ABC
PULS I DIMENSION 11.P NF 12.5 F 13.D CS
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
12/19
11. P
ROTECTION
F
EATURES
Output over
-current protection not included
Reverse input polarity
protection
included unit does not start when input voltage is reversed
Degree of protection
IP 20
EN/IEC 60529
Penetr
ation protection > 3.6mm e.g. screws, small parts
Over
-temperature protection not included
Input transient protection
not included
Output transient protection
included see EMC section
Internal input fuse
not included
12. S
AFETY
F
EATURES
Input / ou
tput separation no galvanic separation Mosfet between input and output
Class of protection
III PE (Protective Earth) or chassis connection not required
PE resistance
< 0.1Ohm between housing and chassis-ground terminal
13. D
IELECTRIC
S
TRENGTH
The input and output voltages have the same reference, are floating and have no ohmic connection to ground.
Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect input/output
terminals together before conducting the test.
When testing, set the cut-off current settings to the value in the table below.
Fig. 13-1 Dielectric strength A
A
Chassis
In- / Output
-
+
Type test 60s 500Vac
Factory test 5s 500Vac
Field test 5s 500Vac
Cut-off current setting > 2mA
PULS nlnnerusnzlru 14. A D F E®IIS LISTED IECEE CB SCHEME I!“ “S £55"; @ IECEx DNV-GL dnvg|.com/af ABS Corrosion IEC 600684-60 Method 4 J
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
13/19
14. A
PPROVALS AND
F
ULFILLED
S
TANDARD
UL 508
UL Certificate
Listed equipment for category NMTR - Industrial Control Equipment
Applicable for US and Canada
E-File: E198865
IEC 60950
-1
CB Scheme Certificate
General safety requirements for Information Technology Equipment
(ITE)
UL 60950-1
UL Certificate
Recognized component for category QQGQ - Information
Technology Equipment (ITE)
Applicable for US and Canada
E-File: E137006
Class I Div 2
CSA Certificate
Power Supplies for Hazardous Location
Applicable for Canada and US
CSA Class: 5318-01 (Canada), 5318-81 (USA)
Temperature Code: T4
Groups: A, B, C and D
ATE
X
Agency Certificate (Bureau Veritas)
EN 60079-0 Explosive atmospheres - General requirements
EN 60079-7, EN 60079-15 Equipment protection by type of
protection "e"
Certificate: EPS 11 ATEX 1 312 X
Temperature Code: T4
Type of Protection: ec
IEC
Ex
IECEx Certificate
IEC 60079-0 Explosive atmospheres - General requirements
IEC 60079-7, IEC 60079-15 Equipment protection by type of
protection "e"
Certificate: IECEx EPS 12.0032 X
Temperature Code: T4
Type of Protection: ec
Marine (DNV GL)
DNV-GL Certificate
DNV-GL Type approved product
Certificate: 12508-10HH
Temperature: Class D
Humidity: Class B
Vibration: Class C
EMC: Class B
Enclosure: Class A
Marine (ABS)
ABS Design Assessment Certificate
ABS (American Bureau of Shipment) assessed product
Certificate: 17-HG1599236-PD
I
EC 60068-2-60
Manufacturer's Declaration (Online Document)
Environmental Tests, Flowing Mixed Gas Corrosion Test
Test Ke - Method 4
H2S: 10ppb
NO2: 200ppb
Cl2: 10ppb
SO2: 200ppb
Test Duration: 3 weeks, which simulates a service life of at least 10
years.
PULS DIMENSION Corrosion G3-lSA-71.04 LABS VDMAZHEAVCHJW 1 5. R C
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
14/19
ISA
-71.04-1985
Manufacturer's Declaration (Online Document)
Airborne Contaminants Corrosion Test
Severity Level: G3 Harsh
H2S: 100ppb
NOx: 1250ppb
Cl2: 20ppb
SO2: 300ppb
Test Duration: 3 weeks, which simulates a service life of at least 10
years
VDM
A 24364
Paint Wetting Impairment Substances Test (or LABS-Test)
Tested for Zone 2 and test class C1 according to VDMA 24364-C1-L/W
for solvents and water-based paints
15. R
EGULATORY
C
OMPLIANCE
EU Declaration of
Co
nformity
The CE mark indicates conformance with the
- EMC directive
- ATEX directive
- RoHS directive
REACH Directive
Manufacturer's Statement
EU-Directive regarding the Registration, Evaluation,
Authorization and Restriction of Chemicals
WEEE
Directive
Manufacturer's Statement
EU-Regulation on Waste Electrical and Electronic Equipment
Registered in Germany as business to business (B2B) products.
EA
C TR Registration
EAC Certificate
EAC EurAsian Conformity - Registration Russia, Kazakhstan
and Belarus
8504408200, 8504409000
PULS UHMENSHJN 16. P 53 25.4 M +-+- IVM ml {4321 Vcw + . es”, I: 20.4 Wldlh 36 W 42" Height 124mm, 4.88“ L—l Depm 127mm, 5 0‘ \- DINrRaH depm
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
15/19
16. P
HYSICAL
D
IMENSIONS AND
W
EIGHT
Weight
340g / 0.75lb
DIN
-Rail Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN-rail height must be added to the unit depth (127mm) to calculate the total required
installation depth.
Installation clearances
See chapter 2
Fig. 15-1 Front view Fig. 15-2 Side view
PULS I DIMENSION 17.A
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
16/19
17. A
CCESSORIES
ZM2.WALL Wall mounting bracket
This standard bracket is used to mount the YR40.241 redundancy module onto a flat surface without utilizing a DIN-
Rail.
Fig. 16-1 ZM2.WALL Wall mounting bracket Fig. 16-2 Assembled wall mounting bracket
ZM11.SIDE Side mounting bracket
This bracket is used to mount the YR40.241 redundancy module sideways with or without utilizing a DIN-Rail.
The two aluminum brackets and the black plastic slider of the unit have to be detached, so that the steel brackets can
be mounted.
For sideway DIN-rail mounting, the removed aluminum brackets and the black plastic slider need to be mounted on
the steel bracket.
Fig. 16-3
ZM11.SIDE Side mounting bracket
Fig. 16-4
Side mounting with DIN-rail brackets
PULS I DIMENSION 18. A N ES ugly/g Q I u I I!!! I!!! [fl ’0
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
17/19
18. A
PPLICATION
N
OTES
18.1. RECOMMENDATIONS FOR REDUNDANCY
Recommendations for the configuration of redundant power systems:
- Use separate input fuses for each power supply.
- Use three-phase power supplies to gain functional safety if one phase fails.
- When single-phase power supplies are utilized connect them to different phases or mains circuits if possible.
- Set the power supply in Parallel-Usemode if this feature is available
- It is desirable to set the output voltages of all power supplies to the same value.
18.2. INDUCTIVE AND CAPACITIVE LOADS
The unit is designed to supply any kind of loads, including unlimited capacitive and inductive loads.
18.3. SIDEWARDS INSTALLATION CLEARANCES
The minimum clearance recommendations are defined in chapter 2.
Normally, the following installation clearance are recommended: 40mm on top, 20mm on the bottom, 5mm on the
left and right sides when the device is loaded permanently with more than 50% of the rated power. Increase this
clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply).
The clearance between the power supplies and the redundancy module can be reduced to zero under the following
conditions:
- 1+1 redundancy application with maximum 20A output current.
- The power supplies are from the PULS DIMENSION series.
- The redundancy module is placed between the two power supplies.
- The output voltage is set to the same level on both power supplies.
0mm
0mm
20A
Load
L1 L2 L3 PE
+ +
- -
Power
Supply
24V,20A DC-
OK
L1 L2 L3 PE
+ +
- -
Power
Supply
24V,20A DC-
OK
YR40.241
Redundancy
Module
Output
Input
1
Input
2
+
-
+
-
+
-
PULS DIMENSION Nuke: Uxe Separate mams synem: cor eazh ppwer supp‘y whenever .1 IS posxrpxe Xe Separate mams synem: cor eazh ppwer supp‘y whenever n r: posxrpxe
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
18/19
18.4. 1+1 REDUNDANCY UP TO 20A
1+1 Redundancy up to 20A requires two 20A power supplies and one YR40.241 redundancy module.
Fig. 17-1 Wiring diagram, 1+1 Redundancy, 20A output current
L1
L2
PE
L3
20A
Load
Failure
Monitor
I I I I I I
L1 L2 L3 PE
+ +
- -
Power
Supply
24V,20A DC-
OK
L1 L2 L3 PE
+ +
- -
Power
Supply
24V,20A DC-
OK
YR40.241
Redundancy
Module
Output
Input
1
Input
2
+
-
+
-
+
-
Note: Use separate mains systems for each power supply whenever it is possible
18.5. N+1 REDUNDANCY, EXAMPLE WITH 60A
N+1 Redundancy up to 60A requires four 20A power supplies and two YR40.241 redundancy modules.
Fig. 17-2 Wiring diagram, n+1 Redundancy, 60A output current
60A
Load
Failure
Monitor
I I II I I I I I
L1
L2
PE
L3
L1 L2 L3 PE
+ +
- -
Power
Supply
24V,20A DC-
OK
L1 L2 L3 PE
+ +
- -
Power
Supply
24V,20A DC-
OK
YR40.241
Redundancy
Module
Output
Input
1
Input
2
+
-
+
-
+
-
L1 L2 L3 PE
+ +
- -
Power
Supply
24V,20A DC-
OK
L1 L2 L3 PE
+ +
- -
Power
Supply
24V,20A DC-
OK
YR40.241
Redundancy
Module
Output
Input
1
Input
2
+
-
+
-
+
-
II I
Note: Use separate mains systems for each power supply whenever it is possible
PULS DIMENSION ,,,,J,,,4,,,L,,,L,,J 0°C orig-nation A Muunling Muunling orienmion c Muunling orienmion n Muunling orienmion E
YR40.241
Y-Series 12-28V, 40A, DUAL REDUNDANCY MODULE
Mar. 2021 / Rev. 1.4 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
19/19
18.6. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig.
17-3
Mounting
Orientation A
(Standard
orientation)
YR40
Redundancy
Module
INPUT
OUTPUT
Output Current
0
20 30 40 50 7C
10
20
30
40A
60
A1
Ambient Temperature
Fig.
17-4
Mount
ing
Orientation B
(Upside down)
YR40
Redundancy
Module
INPUT
OUTPUT
Output Current
0
20 30 40 50 7C
10
20
30
40A
60
A1
Ambient Temperature
Fig.
17-5
Mounti
ng
Orientation C
(Table
-top
mounting)
Output Current
0
20 30 40 50 7C
10
30
40A
60
20
A1
A2
Ambient Temperature
Fig.
17-6
Mounting
Orientation D
(Horizontal cw)
YR40
Redundancy
Module
INPUT
OUTPUT
Output Current
0
20 30 40 50 7C
10
30
40A
60
20
A1
A2
Ambient Temperature
Fig.
17-7
Mounti
ng
Orientation E
(Horizont
al ccw)
YR40
Redundancy
Module
INPUT
OUTPUT
Output Current
0
20 30 40 50 7C
10
30
40A
60
20
A1
A2
Ambient Temperature