Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
3-phase Voltage and Frequency Monitoring with NFC
Description
DPD is a threephase multifunction configurable
monitoring relay suitable for both Delta and
Star mains. It protects loads from wrong phase
sequence, neutral and phase loss, additionally
voltage, frequency and asymmetry thresholds can
be set and provide output signals.
The DPD is delivered with factory default alarm
values, if they are not completely suitable they can
be modified according to own requirements.
DPD has two separate relay outputs.
3 front LEDs provide visual indication of outputs
states and alarm discrimination.
Through the DPD APP the user can reprogram
the unit at any time or check the device operation
status.
Benefits
Flexibility and Versatility. 2 part numbers cover all
requirements in terms of mains type, voltage and
frequency values.
2 SPDT outputs. It is possible to provide 2 different
signals for different purposes.
Plug & Play. DPD is available with 2 different factory
settings. Which are the most commonly used.
Customized devices availability. DPD can be ordered
with customized settings also for very small quantities.
NFC Communication. Through the NFC communication,
via smartphone, tablet or PC, the DPD can be configured
or provide real time operation data such as: alarms
status, voltage & frequency readings.
High Compactness. The DPD features a large amount
of capabilities in just 22.5 mm.
Applications
DPD is suitable for all applications where it is necessary to monitor phase presence, correct phase sequence
and the voltage, frequency and quality of threephase load mains: lifts, escalators, HVAC, material handling,
pumps and compressors.
Main functions
3Ph or 3Ph+N monitoring
From 177V to 552V LL or 102V to 318V LN
Operating frequency from 45 to 440Hz
Phase sequence and phase or neutral loss alarm
2
Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
Configurable voltage, frequency and asymmetry alarms
Up to 10 alarms combinable with and / or operators
NFC Interface
Structure
LED2
LED1
LED3
B
A
C
Element Component Function
APower supply terminals L1, L2, L3 and N supply and measuring terminals
BOutput2 terminals Output relay 2 contacts terminals: COM, NO and NC
COutput1 terminals Output relay 1 contacts terminals: COM, NO and NC
LED1 Output led This LED is lit when Output 1 is energized
LED2 Output led This LED is lit when Output 2 is energized
LED3 Alarm led
LED3 is bicolor and can be blinking or fixed:
Green On fixed: ok
Green Flashing: alarm triggered but configured delay is elapsing
1 red flash: phase or neutral Loss or phase sequence
2 red flashes: under or over voltage
3 red flashes: under or over frequency
4 red flashes: asymmetry
5 Flashes: out of range parameter
22.5 mm 84 mm [3307”] mm GAVAIZI V
3
Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
Features
General
Material PA66 or Nylon
Assembly DIN rail mounting (According to EN 50022)
Protection grade IP20
Weight 120g
Terminals Screw terminals. AWG30 to AWG14 (0.06 mm2 to 2.1 mm2) stranded or solid
22.5 mm
84 mm [3,307”]
99.5 mm [3,917”]
[0,885”]
Power Supply
Power supply
Voltage range: 166 V to 576 V (208 V -20% to 480 V +20%) line to line voltage
Frequency range: 45 Hz to 440 Hz (50 Hz -10% to 400 Hz +10%) sinusoidal wave-
form
Consumption < 3 VA
Power ON Delay Configurable from 0 to 6 s (default 0 s)
Environmental
Working temperature -20° C to 60° C (-4° F to 140° F)
Storage temperature -30° C to 80°C (-22° F to 176° F)
Relative humidity 5-95% non condensing
Pollution degree 2
Operating max altitude 2000m
Salinity No saline environment
UV resistance No UV exposure
CEQ‘MLE.
4
Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
Vibration/Shock resistance
Tests with the device outside
the box:
Vibration response
(IEC60255-21-1)
Vibration endurance
(IEC 60255-21-1)
Shock (IEC 60255-21-2)
Bump (IEC 60255-21-2)
Class1
Class1
Class1
Class1
Tests with the device inside the
box:
Vibration, random
(IEC60068-2-64)
Shock (IEC 60255-21-2)
Bump (IEC 60255-21-2)
Class1
Class1
Class1
Note:
Class 1: normal use in industrial plants, normal transportation condition.
Compatibility and conformity
Approvals
CE Marking LV directive, EMC directive EN 60947-5-1
Inputs
Measuring ranges
Variable measuring
Voltage 3PH (Delta) or 3PH+N (Star) line measurement on L1, L2, L3 and N lines
Frequency 3PH (Delta) or 3PH+N (Star) line measurement on L1, L2, L3 and N lines
Asymmetry measurement on L1, L2, L3 and N lines
Phase loss
Neutral loss
Phase sequence
Out range measurement
Out of bounds parameter
Voltage measurement
Typology 3PH (Delta) or 3PH+N (Star) line voltage measurement on L1, L2, L3 and N lines
Nominal Range for Line 3PH
(Delta) 177 V to 552 V (delta voltage 208 V-15% to 480 V+15%)
Nominal Range for Line 3PH+N
(Star) 102 V to 318 V (star voltage 120 V-15% to 277 V+15%)
Adjustable Threshold range 3PH (Delta) 177 VAC to 552 VAC, 3PH+N (Star) 102 VAC to 318 VAC
Adjustable Hysteresys From 2% to 5%
Delay ON From 0 s ( <200 ms ) to 60 s
Delay OFF 0 s ( <200 ms ) to 60 s
Resolution 1 V
Accuracy 1% reading +1 V
Refresh time According to alarms response time
mm GAVAIZI V
5
Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
Frequency measurement
Typology 3PH (Delta) or 3PH+N (Star) line frequency measurement on L1, L2, L3 and N lines
Adjustable threshold range From 45 Hz to 440 Hz
Adjustable hysteresys From 2% to 5%
Delay ON From 0 s (<200 ms) to 60 s
Delay OFF
Resolution 0.5 Hz
Accuracy 1% reading
Refresh time According to alarms response time
Asymmetry measurement
Typology 3PH (Delta) or 3PH+N (Star) line asymmetry measurement on L1, L2, L3 and N lines
Adjustable threshold range From 0% to 30%
Adjustable hysteresys From 2% to 5%
Delay ON From 0 s (<200 ms) to 60 s
Delay OFF
Resolution Compatible with direct measurements
Accuracy
Refresh time Compatible with alarm delay time
Non priority alarms (up to 10 configurable alarms)
Input variables Over-voltage, under-voltage, over-frequency, under-frequency, asysmmetry
Reaction time ≤ 200 ms
Phase loss priority alarm
Input variables L1-L2, L2-L3 and L3-L1 Voltage measurements
Adjustable threshold range From 60% to 90%
Reaction time ≤ 200 ms
Hysteresis From 2% to 5%
Delay ON From 0 s (<200 ms) to 60 s
Delay OFF
Neutral loss priority alarm
Input variables L1-N, L2-N and L3-N Voltage measurements.
Adjustable threshold range From 10% to 30% of LN voltage.
Reaction time ≤ 200ms
Adjustable hysteresys From 2% to 5%
Delay ON From 0s (<200ms) to 60s
Delay OFF
Phase sequence priority alarm
Input variables Connection L1, L2, L3, N
Range No setting necessary
Reaction time ≤ 200 ms
Hysteresis
NoneDelay ON
Delay OFF
Measure out of range priority alarm
Input variables Measure voltage, frequency, asymmetry
Range No setting necessary
Reaction time ≤ 200 ms
Hysteresis
NoneDelay ON
Delay OFF
6
Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
Outputs
Type 2 x SPDT electromechanical relay with change-over contacts
Logic
Priority alarms:
Output 1 De-Energized on Alarm
Output 2 De-Energized on Alarm
Non Priority Alarms:
Output 1 N.E. or N.D. according to Configuration ( Default N.E. )
Output 2 N.E. or N.D. According to Configuration ( Deafult N.E. )
N.E. = Normally Energized
N.D. = Normally De-Energized
Contact rating
AC1: 8A @ 250 VAC
DC12: 5 A @ 24 VDC
AC15: 2.5 A @ 250 VAC
DC13: 2.5 A @ 24 VDC
Insulation
Terminals Basic Insulation
Inputs: L1,L2,L3,N to Output 1:
15,16,18 2.5KVrms, 4KV impulse 1.2/50us (basic)
Inputs: L1,L2,L3,N to Output 2:
25,26,28 2.5KVrms, 4KV impulse 1.2/50us (basic)
Output 1: 15,16,18 to Output 2:
25,26,28 2.5KVrms, 4KV impulse 1.2/50us (basic)
Operating Description
Suitability
DPD can be used for power supply and mains quality monitoring of all threephase loads with supply voltage
from 102VAC to 552VAC. Monitoring function can be performed between Line to Line as well as Line to Neutral.
Alarms
There are 2 types of alarms for the DPD: the "priority" alarms and the "non priority" alarms.
Priority alarms De-Energize both outputs at the same time when they are triggered:
Phase loss
Neutral loss ( only in "Star" configured systems )
Wrong phase sequence
Out of range measurement
Each one of the priority alarm can be disabled individually. The threshold can be set for the phase or neutral
loss.
Non priority alarms are totally configurable by user. Type of measurement to be monitored and trigger value
can be freely set, within the specified ranges, and changed any time:
Undervoltage U<
Overvoltage U>
Overfrequency f>
Underfrequency f<
Threephase asymmetry
mm GAVAIZI V
7
Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
Up to 10 virtual alarms among the above types can be configured. As there are only 2 outputs on the DPD,
certain alarms can be configured without being directly associated to an output.
Delays
For each one of the Alarms it is possible to set an "Alarm ON" from 0 ( the device reaction time is though <0.2
s ) to 60 s. If the alarm cause restores before alarm ON delay elapsing no output signal will be provided. Alarm
OFF delay can be set from 0 s to 600 s.
Delays are only applicable for non priority alarms. Priority alarms are always immediate.
Outputs
There are 2 SPDT Electromechanical outputs which can be associated to any of the alarms set. It is also
possible to associate 2 o more alarm by means of AND or OR operators to a specific output.
Each ones of the outputs can be configured as "Normally Energized" or "Normally De-Energized".
Visual information
The DPD is equipped with 3 LEDs which provide the status information
LED1 is lit when the Output 1 is energized
LED2 is lit whne the Output 2 is energized
LED3 is bicolor and can be blinking or fixed
LED3 key:
LED3 Status
Green On fixed OK
Green Flashing Alarm triggered but configured delay is elapsing
1 red flash Phase or neutral Loss or phase sequence
2 red flashes Under/over-voltage
3 red flashes Under/over-frequency
4 red flashes Asymmetry
5 Flashes Out of range parameter
NFC communication
DPD is equipped with built-in NFC communication.
With the DPD APP through the NFC communication it is possible to read or write the device configuration as
well as reading the voltage, the frequency or the alarms in real time.
NFC communication does not require any power for the device configuration.
DPDs can be configured without taking them out of the box.
Configuration
The configuration can be prepared on the PC or smartphone, downloaded from another device, by means of
NFC, or picked from file.
Once a configuration has been prepared on the PC it can be uploaded to one of more DPDs.
NFC also allows, when necessary to download the configuration from a device, modify it if necessary and then
upload it to another device.
It is possible to Lock the DPD in order to avoid tampering or unauthorized configuration. The locking/ unlocking
procedure is managed through one of the available apps.
Operation flow
When powered, after Power On delay elapsing, until mains parameters are within all the alarms threshold
values, the DPD LED3 will be lit green (steady ).
If one of the mains parameters is exceeded the alarm ON delay elapsing starts, LED3 blinks green ( if a delay
is set, else immediately ), at the end of the delay the alarm associated output switches and LED3 flashes RED
( see visual information table ).
cum) GAVAIZI V max \AV M Van: sz L3 VLm L2 L3 Var.) L2 max \AVWH‘ : \VurJ-V'm max \AVPW‘ = 0 2 ASY = 0 max \VMM-VPHM : \VWM-V'JM max \Vmewn\ : \Vmam’V'L‘ J : \Vmelm‘ : \Vme' “7.1
8
Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
When the value, which was exceeded, returns to normal the delay OFF elapsing starts ( if a delay is set, else
immediately ), at the end of the delay the alarm associated output switches returning to original position. LED3
returns to steady green.
Phase loss
Phase loss measurement is performed by comparing the 3 phases voltage values. If the voltage of one phase
falls below the set threshold, can be turned OFF if unwanted, ( default is 85%), compared to the other 2
phases, the alarm goes off. DPD detects loads regenerated voltage. Setting below the default value may cause
insensitivity to phase loss.
Neutral loss
On Star connected loads if the neutral connection is lost the DPD detects the failure and goes into alarm.
Setting the neutral loss above the default value may cause, in case of a balanced load, insensitivity to neutral
loss.
This detection can be turned OFF if unwanted.
Asymmetry
Asymmetry is an indicator of the mains quality, can be turned OFF if unwanted, and it is defined as the
absolute value of the maximum deviation among the mains voltages, divided by the nominal voltage of
the 3-phase system. The definition changes according to the voltage reference:
1) In case of measuring phase-phase voltages:
max |∆V
PH-PH
|
V∆NOM
x
100
Fig. 1 Phase-phase monitoring
cum) Mum max \Av M L3 L \AVpHuF‘ \ \A \ 3 \VNoM-VWN‘ \VmM-VLN \VNom-VmF‘ = F‘
9
Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
2) In case of measuring phase-neutral voltages:
max |∆V
PH-N
|
VNOM
x
100
L1
N
L3 L2
max V
PH-N
=V’ -V’
L3-N L2-N
N’
V=VL1-NNOM L2-N L3-N
=V =V L1
N
L3 L2
L1
L3’ L2’
V’L3-N
V’L2-N
max V
PH-N
=0 ASY=0
max V
NOM
-V =V -V’ =V -V’ =V -V’
PH-N NOML1-NNOM L2-N NOML3-N
YYYY
max V
NOMPH-NNOM L3-N
-V =V -V’
YY
Y
Fig. 2 Phase-neutral monitoring
10
Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
Motor load application block diagram
L1, L2, L3, N
L1, L2, L3, N Alarm Signaling
Load
Alarm Signaling
Lamp
L1, L2, L3, N
NFC Protocol
Software interface
NFC Protocol
Power supply
Fuse
Motor
Status LED
11
Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
Connection Diagrams
N1
5
L1 L2 L3 16 18 26 28
mm GAVAIZI V
12
Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
References
Further reading
Information Where to find it QR
Installation manual http://www.productselection.net/MANUALS/UK/dpd_im.pdf
User manual http://www.productselection.net/MANUALS/UK/dpd_um.pdf
Google App https://play.google.com/store/apps/details?id=us.belka.dpd&hl
Windows desktop app www.productselection.net/Download/UK/Setup_DPD.msi
NFC drivers www.productselection.net/Download/UK/ACR1252_Winx64_64bit.zip
www.productselection.net/Download/UK/ACR1252_Winx86_32bit.zip
CARLO GAVAZZI compatible components
Purpose Component name/code Notes
USB NFC reader / writer ACR1252U
This accessory is necessary to
interface the DPD NFC with a PC
which is not equipped with NFC
transmission
13
Carlo Gavazzi Controls S.p.A.
DPD
DPD DS ENG16/11/2017
Ordering code
DPD02DM44 (Default 1)
DPD02DM44B (Default 2)
Country default settings
Page Item Part number
DPD02DM44 DPD02DM44B
Grid type
Line type Delta Delta
Rated line voltage 400 VAC 240 VAC
Power ON delay 0 s 0 s
Setpoints
Alarm 1 Overvoltage Overvoltage
Voltage Value 440 VAC 264 VAC
Hysteresys 2% 2%
Delay ON 0 s 0 s
Delay OFF 0 s 0 s
Alarm 2 Undervoltage Undervoltage
Voltage Value 360 VAC 216 VAC
Hysteresys 2% 2%
Delay ON 0 s 0 s
Delay OFF 0 s 0 s
Priority alarms
Phase loss enable ON ON
Phase loss threshold 85% 85%
Neutral loss Not active Not active
Phase sequence enable ON ON
Out of range measurement ON ON
Output 1
Assignment Alarm 1 Alarm 1
Logic Normally energized Normally energized
Logic operators None None
Output 2
Assignment Alarm 2 Alarm 2
Logic Normally energized Normally energized
Logic operators None None
COPYRIGHT ©2017