Introduction
Laird Outdoor Cooler Series is an Air to Air thermoelectric assembly that uses impinge-
mentflowtotransferheat.Itoffersdependablecompactperformancebycooling
objectsviaconvectionandisdesignedtoprovidecoolingforawiderangeofoutdoor
environments in the telecom, industrial and kiosk markets. They are intended to work
inanopenloopsystemorifpurchasedwithabi-directionalcontrollerinaclosedloop
system with feedback control.
Heat is absorbed and dissipated thru high density heat exchangers equipped with air
ductedshroudsandbrandnamefans.Theheatpumpingactionoccursfromcustom
designedthermoelectricmodulesthatachieveahighcoefficientofperformance(COP)
tominimizepowerconsumption.
This product series has been designed to pass rigorous Telcordia test requirements for
outdoorenvironments.Thisisduetotheselectionofworldclasscomponentssuchas
brandfanswiththehighestdegreeofenvironmentalprotection,waterproofconnectors,
heavydutyanodizationontheheatexchangers,anddoubleenvironmentalsealsforthe
thermoelectric modules.
Thismanualprovidesthenecessarygeneralinformationforproperinstallationandop-
erationthathasbeendevelopedtoachievethebestresultswhenusingaLairdOutdoor
Cooler Series product.
Incoming Inspection
Laird Outdoor Coolers are designed, built, and packaged to withstand the shock and
vibrationassociatedwithnormaltransitmeansbycommoncarriers.Occasionally,im-
proper handling during shipment may cause damage to the product. Therefore, packag-
es should be opened promptly and inspected for damage. Any packaging tears, dents,
scratches, or loose objects should be noted on the Freight Bill. If damage is found, an
immediateclaimmustbefiledwiththefreightcarrier.Retainallpackingmaterials.
LairdcannotberesponsibleforConsignee’sfailuretofileafreightclaiminatimely
manner.
General Safety & Warning
WARNING
Electrical Shock Hazard
INSTALL UNIT TO CABINET WALL FIXTURE PRIOR TO POWERING DEVICE. OPERATIONAL
VOLTAGE SHOULD COMPLY TO NOMINAL RATING ON LABEL. ENSURE THAT THERE IS AN
EXTERNAL FUSE IN LINE WITH OUTDOOR COOLER TO PROTECT INPUT POWER LINES TO
UNIT
THR-UM-AA-480-XX_03154www.lairdtech.com
Specifications
ThebelowspecificationtableshowsratingsforastandardAA-480OutdoorCoolerunit
withoperationateither24VDCor48VDC.
Technical
Technology Thermoelectricmodules,forcedair,closedloop(not
mixingwithoutsideair),filter-less,non-refrigerant
CoolingatdT=0°C,andnominal/floatvoltage.1 480/529W(1638/1805Btu/hr)
Heating2 450W(1535Btu/hr)
Voltage(nominal/maximum) 24/28VDC|48/60VDC
Currentdraw,±10%(nominal) 19.3Amps|9.7Amps
Grounding(allvoltages) Positiveornegative
Weight 13.2kg(29.1lbs)
Panelmounting Through mount
Fanlife(L10at+40°C) Cold side 57,500hr, Warm side 75,000hr
Connector type Terminalblockwithcageclamp(12-28AWG)
Hi-pottesting 707 VDC
Environmental
Temperaturerange3(externalambient) -40°Cto+55°C(-40°Fto+131°F)
Temperaturerange(internalenclosure) -20°Cto+55°C(-4°Fto+131°F)
Degreeofprotection,enclosure4 NEMA4(IP55)
Degreeofprotection,unit5 IP54
Soundlevel(1mdistance) 65dB(A)
Over-TempThermostat(hotandcoldsideheatsink) -
1) Coolingcapacitiesatnominal/floatvoltageareratedatexternaltemperaturesof35°Cand50°Crespectively.Floatvoltageis
definedat28VDCfor24voltversionor54VDCfor48voltversion.
2) Heatingcapacityisratedatexternaltemperatureof-40°C,nominalvoltage,andΔT=45°C.
3) Controllerfunctionshouldnotoperatetheexternalfanduringheatingmode.Thiswillpullheatoutofthecabinet.
4) Thehighestenvironmentalprotectionlevelrequiresanexternalshroudandisdefinedastheprotectionlevelfortheenclo-
sure.
5) Ratingforunitwithoutprotectiveshroud.
Note:ThespecifiedperformanceofanyLairdcoolingunitisdependentonhowitishandledandincorporatedintothefinal
product.Thisincludeselementssuchasthesystemdesign,insulationdesign,andassemblymethod.WhileLairdisableto
providegeneralguidelinesbaseduponourexperience,itisultimatelytheresponsibilityoftheOEMtovalidateeachproduct
and its performance for its intended use.
Technical Specifications
LairdTEAproductnomenclaturecanbedefinedasfollows:
HEAT
TRANSFER
AA
(AirtoAir)
100Watts
150Watts
200Watts
250Watts
480Watts
24VDC
48VDC
IP44
IP54
00-XX
Open loop, no temperature control
LE-XX
Closedloop,thermostaticcontrol
(coolingmode>35C,heatingmode<5C)
LK-XX
Closedloop,thermostaticcontrol
(coolingmode>25C,heatingmode<10C)
COOLING
POWER
VOLTAGE FANS TEMPERATURE
CONTROLLERS
ConsultwithLairdforcustomdesignedbi-directionalcontrolfeatures,alarmsor
self start checks.
Cooling power Pc vs dT
LZZL
62v 265
THR-UM-AA-480-XX_03155www.lairdtech.com
Performance Curve
Thecoolingcapacitywasconductedatanambienttemperatureof35°C.Performance
willdeviatebasedonambienttemperaturecondition.
Isometric Drawing
306
316
96
330
Φ5.5 (8x)
280
280
59.3
122.1 43.9
306
3
Sealing gasket
Sealing gasket
330
303
171.4
57.6
306
02052510 3015 35 40
Pc (W)
ΔT (°C)
600
500
400
300
200
100
0
PERFORMANCE Pc VS ΔT
THR-UM-AA-480-XX_03156www.lairdtech.com
Installation and Operation Instructions
ReducingthepassiveheatloadiscriticaltoyieldthehighestefficiencyoutofanOutdoor
Cooler and maximize service life. It is important to insulate the walls of an enclosure
withasmuchinsulationmaterialaspermissiblewithoutinterferingwithnearbyelec-
tronicsorsystemlevelobstructions.Properinsulationoftheenclosurecanresultin
sizing a smaller Outdoor Cooler unit and power supply, which can reduce total system
costs.
The Outdoor Cooler is mounted onto a cabinet wall with “Hot Side” mounted external
to cabinet. This is required to dissipate heat out of the cabinet. It is also important to
havegoodventilationonthehotsidetotransportheatexhaustawayfromthecabinet.
At minimum of one fan thickness is required from the wall surface to the exterior face of
the fan to allow air to enter into the fan and transport the exhaust through the ducted
shroud.
Outdoor Coolers cool below ambient, so it is important to run them in a cabinet that
is sealed from the outside environment. If the dew point is reached, then moisture in
the air will condense onto the cold side heat exchanger. Access to outside air exchange
canacceleratethemoisturecondensationrateandcauselargeamountsofmoistureto
accumulateonthecoldsurfacesoftheOutdoorCooler,whichcoulddegradeoperation
lifeovertimeifthesystemisnotdesignedtodraincondensation.Itisrecommendedto
mounttheOutdoorCoolerinaverticalorientation,socondensationrunsoffthecold
side heat exchanger. If the enclosure cannot accommodate this, then the Outdoor Cool-
ershouldbeinstalledataminimum15degreeangleinhorizontalorientationtoallow
forcondensationtorunoffthecoldsideheatexchanger.
The Outdoor Cooler must be protected from vandalism or external forces that may
bump up against unit and cause damage.
Mounting & Hardware
The enclosure should be sealed from the outside environment by maintaining good
compression between the Outdoor Cooler and cabinet wall. The Outdoor Coolers are
designed to be through mount, so a cut out on the enclosure wall will be required to
accommodatethecoldsideheatexchanger.Referencethebelowdiagramformounting
holelocationsandcoldsideheatexchangerdimensions.Thecutoutshouldbe2.5mm’s
largerthanthecoldsideheatexchanger.Eightmountingholesareavailabletofasten
theOutdoorCoolerunittocabinetwall.Themountingholesaredesignedtoaccom-
modate M5 machine hardware as shown in diagram. External tooth lock washers are
recommendedtopreventOutdoorCoolerfromlooseningovertime.
280
330
96
\/
+
‘“\HWH\1‘\H\HH\\HH\\H\HHHHHHHHHW“
05.5 (8x)
/
4k
’ “‘HHHHH\“\\HHW\H\HHHHHH‘WHHW “
H—
316
306
THR-UM-AA-480-XX_03157www.lairdtech.com
306
316
96
330
Φ5.5 (8x)
280
280
59.3122.1 43.9
306
3
Sealing gasket
Sealing gasket
330
303
171.4
57.6
306
Tooth washer
Nut
Cabinet wall
Machine screw
Flat washer
TE-unit
comma nun Imwnx
mu
"mam
am
TERMINM
sLCItK WITN
I magnum
2w TEM BLOCK 24v mm BLOCK
INT mu- I
luv m» I
m m. I
m W I
my
"IA
24v 1:»: BLOCK
24v mm mm
mm
I
I
"IA I
I
I
I
THR-UM-AA-480-XX_03158www.lairdtech.com
Schematic
Outdoor Coolers come with a durable simple to use cage clamp. Wires should be
strippedback6mm’sinlengthandinsertedintoconnector.Connectorcanaccommo-
datewiresizesof12to28AWG.ForinputpowertoTEM16AWGstrandedcopper
wire is recommended. For input power to fans 18 AWG stranded copper wire is
recommended.
InternalschematicofOutdoorCoolerUnit.(24Voltschematicshown)
1. Connect external fuse in line with input power connector to protect input power
linesfromshorting.
2.Inputvoltagemustnotexceedratingonlabelofunit.Maximumripplecurrent
should not exceed three percent of nominal value.
THR-UM-AA-480-XX_03159www.lairdtech.com
Serviceability
NospecialmaintenanceisrequiredwhenusingLairdOutdoorCoolers.Forcontinued
optimalperformanceandextendedlifeoftheunit,itisrecommendedtocleanthe
(internal/external)heatsinksandfansperiodicallyastheywillaccumulatedustfrom
outsidecontaminantsovertime.IfaunitisnotperformingproperlyconsultwithLaird.
Warranty
Laird Outdoor Coolers are manufactured in an ISO 9001:2008 facility. Units adhere to
the highest quality standards and are free from defects in material, components, and
workmanship. This warranty covers repair or replacement of product, to be done at a
Lairdfacility,foraperiodoftwo(2)yearsfromdateofshipment.Customerisresponsi-
ble for shipping product to Laird freight prepaid. Laird in turn will return the warranted
producttocustomerfreightprepaid,ifwithinthetimeperiodspecifiedabove.Warranty
coverageisineffectwhenthefollowingoperatingconditionsarecontinuouslysatisfied:
• AmbientTemperatureRangewithin-40°Cto55°C.
• LineVoltagevariationwithinplusorminus10%ofnameplaterating.
Inaddition,thefollowingcriteriamustbemet:
• Electricalinstallationandgroundingmustcomplywithlocalelectricalandsafety
codes.
• Outdoor Cooler must be used in the environment for which it is designed.
• Customercannotabuseormishandletheproductinanyway.Anymodificationsto
the original unit will also void warranty.
• CompliancetoUser’sManualoranyotherinstructionalguideprovidedbyLairdfor
the product.
This warranty does not cover the following:
• Applicationswhereproductisbeingmisapplied.Thisincludesinappropriate
selectionofOutdoorCoolerfortheenvironmentandconditionsinwhichitistobe
used.
• Damagescausedbyshippingcarrieroranyotheraccidentafterproducthasleft
Laird. Shipping claims are the responsibility of the customer and are to be com-
pletedinatimelymanner.
• Reimbursementoflaborforinstallationorremovalofwarrantedproduct,orfor
partsandlaborresultingfromrepairsperformedbyanyothersourcebesidesLaird.
This is the complete warranty and is in lieu of any other warranty expressed or implied,
includingbutnotlimitedtoanyimpliedwarrantyofmerchantabilityorfitnessfora
particularpurpose.Lairdwillinnowaybeliableforincidentalorconsequentialdamage
whatsoeverorforanyotherclaimsbythecustomerfordamagesinconnectionwith
Laird products, even if advised in advance of the possibility of such damage.
THR-UM-AA-480-XX_031510 www.lairdtech.com
Return Procedure
AllreturnsmustbeassignedaNon-ConformanceMaterialReturnAuthorizationnumber
(NCMR#)inadvance.ReturnsreceivedwithoutRMA#mayberefused.Intheevent
that a return is required, the Customer should call Laird Customer Service Department
atUSA:+1.919.597.7300,Europe:+46.31.420530,Asia:+86.755.2714.1166orsendan
emailtoorder.gothenburg@lairdtech.com.TheCustomerwillbeaskedtofilloutan
NCMR form so that NCMR number can be issued. All returns must be securely packed
to prevent shipping damage and must be clearly marked with the NCMR number on the
box. Consignor shall pay freight charges on all returns.
La'rd)
SmarKTemno‘ogy Delweved '
THR-UM-AA-480-XX_0315
Any information furnished by Laird and its agents is believed to be accurate and reliable. All specifications are subject to change without notice. Responsibility for the use and
application of Laird materials rests with the end user, since Laird and its agents cannot be aware of all potential uses. Laird makes no warranties as to the fitness, merchantability
or suitability of any Laird materials or products for any specific or general uses. Laird, Laird Technologies, Inc or any of its affiliates or agents shall not be liable for incidental or
consequential damages of any kind. All Laird products are sold pursuant to the Laird Terms and Conditions of sale in effect from time to time, a copy of which will be furnished
upon request. © Copyright 2015 Laird Technologies, Inc. All Rights Reserved. Laird, Laird Technologies, the Laird Logo, and other marks are trademarks or registered trademarks
of Laird Technologies, Inc. or an affiliate company thereof. Other product or service names may be the property of third parties. Nothing herein provides a license under any Laird
or any third party intellectual property rights.
Americas:+1.919.597.7300
Europe:+46.31.420530
Asia:+86.755.2714.1166
www.lairdtech.com
order.gothenburg@lairdtech.com