Laird Thermal Systems, Inc. 的 AA-480-XX User Manual 规格书

Laird" Smart Technology. Delivered."
AA-480-XX
OUTDOOR THERMOELECTRIC
COOLER ASSEMBLY
USER’S MANUAL
THR-UM-AA-480-XX_03152www.lairdtech.com
Table of Contents
Introduction 3
IncomingInspection 3
GeneralSafety&Warnings 3
TechnicalSpecifications 4
InstallationandOperationInstructions 6
Serviceability 9
Warranty 9
Return Procedure 10
Americas:+1.919.597.7300
Europe:+46.31.420530
Asia:+86.755.2714.1166
www.lairdtech.com
ets.sales@lairdtech.com
THR-UM-AA-480-XX_03153www.lairdtech.com
Introduction
Laird Outdoor Cooler Series is an Air to Air thermoelectric assembly that uses impinge-
mentflowtotransferheat.Itoffersdependablecompactperformancebycooling
objectsviaconvectionandisdesignedtoprovidecoolingforawiderangeofoutdoor
environments in the telecom, industrial and kiosk markets. They are intended to work
inanopenloopsystemorifpurchasedwithabi-directionalcontrollerinaclosedloop
system with feedback control.
Heat is absorbed and dissipated thru high density heat exchangers equipped with air
ductedshroudsandbrandnamefans.Theheatpumpingactionoccursfromcustom
designedthermoelectricmodulesthatachieveahighcoefficientofperformance(COP)
tominimizepowerconsumption.
This product series has been designed to pass rigorous Telcordia test requirements for
outdoorenvironments.Thisisduetotheselectionofworldclasscomponentssuchas
brandfanswiththehighestdegreeofenvironmentalprotection,waterproofconnectors,
heavydutyanodizationontheheatexchangers,anddoubleenvironmentalsealsforthe
thermoelectric modules.
Thismanualprovidesthenecessarygeneralinformationforproperinstallationandop-
erationthathasbeendevelopedtoachievethebestresultswhenusingaLairdOutdoor
Cooler Series product.
Incoming Inspection
Laird Outdoor Coolers are designed, built, and packaged to withstand the shock and
vibrationassociatedwithnormaltransitmeansbycommoncarriers.Occasionally,im-
proper handling during shipment may cause damage to the product. Therefore, packag-
es should be opened promptly and inspected for damage. Any packaging tears, dents,
scratches, or loose objects should be noted on the Freight Bill. If damage is found, an
immediateclaimmustbefiledwiththefreightcarrier.Retainallpackingmaterials.
LairdcannotberesponsibleforConsignee’sfailuretofileafreightclaiminatimely
manner.
General Safety & Warning
WARNING
Electrical Shock Hazard
INSTALL UNIT TO CABINET WALL FIXTURE PRIOR TO POWERING DEVICE. OPERATIONAL
VOLTAGE SHOULD COMPLY TO NOMINAL RATING ON LABEL. ENSURE THAT THERE IS AN
EXTERNAL FUSE IN LINE WITH OUTDOOR COOLER TO PROTECT INPUT POWER LINES TO
UNIT
THR-UM-AA-480-XX_03154www.lairdtech.com
Specifications
ThebelowspecificationtableshowsratingsforastandardAA-480OutdoorCoolerunit
withoperationateither24VDCor48VDC.
Technical
Technology Thermoelectricmodules,forcedair,closedloop(not
mixingwithoutsideair),filter-less,non-refrigerant
CoolingatdT=0°C,andnominal/floatvoltage.1 480/529W(1638/1805Btu/hr)
Heating2 450W(1535Btu/hr)
Voltage(nominal/maximum) 24/28VDC|48/60VDC
Currentdraw,±10%(nominal) 19.3Amps|9.7Amps
Grounding(allvoltages) Positiveornegative
Weight 13.2kg(29.1lbs)
Panelmounting Through mount
Fanlife(L10at+40°C) Cold side 57,500hr, Warm side 75,000hr
Connector type Terminalblockwithcageclamp(12-28AWG)
Hi-pottesting 707 VDC
Environmental
Temperaturerange3(externalambient) -40°Cto+55°C(-40°Fto+131°F)
Temperaturerange(internalenclosure) -20°Cto+55°C(-4°Fto+131°F)
Degreeofprotection,enclosure4 NEMA4(IP55)
Degreeofprotection,unit5 IP54
Soundlevel(1mdistance) 65dB(A)
Over-TempThermostat(hotandcoldsideheatsink) -
1) Coolingcapacitiesatnominal/floatvoltageareratedatexternaltemperaturesof35°Cand50°Crespectively.Floatvoltageis
definedat28VDCfor24voltversionor54VDCfor48voltversion.
2) Heatingcapacityisratedatexternaltemperatureof-40°C,nominalvoltage,andΔT=45°C.
3) Controllerfunctionshouldnotoperatetheexternalfanduringheatingmode.Thiswillpullheatoutofthecabinet.
4) Thehighestenvironmentalprotectionlevelrequiresanexternalshroudandisdefinedastheprotectionlevelfortheenclo-
sure.
5) Ratingforunitwithoutprotectiveshroud.
Note:ThespecifiedperformanceofanyLairdcoolingunitisdependentonhowitishandledandincorporatedintothefinal
product.Thisincludeselementssuchasthesystemdesign,insulationdesign,andassemblymethod.WhileLairdisableto
providegeneralguidelinesbaseduponourexperience,itisultimatelytheresponsibilityoftheOEMtovalidateeachproduct
and its performance for its intended use.
Technical Specifications
LairdTEAproductnomenclaturecanbedefinedasfollows:
HEAT
TRANSFER
AA
(AirtoAir)
100Watts
150Watts
200Watts
250Watts
480Watts
24VDC
48VDC
IP44
IP54
00-XX
Open loop, no temperature control
LE-XX
Closedloop,thermostaticcontrol
(coolingmode>35C,heatingmode<5C)
LK-XX
Closedloop,thermostaticcontrol
(coolingmode>25C,heatingmode<10C)
COOLING
POWER
VOLTAGE FANS TEMPERATURE
CONTROLLERS
ConsultwithLairdforcustomdesignedbi-directionalcontrolfeatures,alarmsor
self start checks.
Cooling power Pc vs dT LZZL 62v 265
THR-UM-AA-480-XX_03155www.lairdtech.com
Performance Curve
Thecoolingcapacitywasconductedatanambienttemperatureof35°C.Performance
willdeviatebasedonambienttemperaturecondition.
Isometric Drawing
306
316
96
330
Φ5.5 (8x)
280
280 
59.3
122.1 43.9
306
3
Sealing gasket
Sealing gasket
330
303
171.4
57.6
306
02052510 3015 35 40
Pc (W)
ΔT (°C)
600
500
400
300
200
100
0
PERFORMANCE Pc VS ΔT
THR-UM-AA-480-XX_03156www.lairdtech.com
Installation and Operation Instructions
ReducingthepassiveheatloadiscriticaltoyieldthehighestefficiencyoutofanOutdoor
Cooler and maximize service life. It is important to insulate the walls of an enclosure
withasmuchinsulationmaterialaspermissiblewithoutinterferingwithnearbyelec-
tronicsorsystemlevelobstructions.Properinsulationoftheenclosurecanresultin
sizing a smaller Outdoor Cooler unit and power supply, which can reduce total system
costs.
The Outdoor Cooler is mounted onto a cabinet wall with “Hot Side” mounted external
to cabinet. This is required to dissipate heat out of the cabinet. It is also important to
havegoodventilationonthehotsidetotransportheatexhaustawayfromthecabinet.
At minimum of one fan thickness is required from the wall surface to the exterior face of
the fan to allow air to enter into the fan and transport the exhaust through the ducted
shroud.
Outdoor Coolers cool below ambient, so it is important to run them in a cabinet that
is sealed from the outside environment. If the dew point is reached, then moisture in
the air will condense onto the cold side heat exchanger. Access to outside air exchange
canacceleratethemoisturecondensationrateandcauselargeamountsofmoistureto
accumulateonthecoldsurfacesoftheOutdoorCooler,whichcoulddegradeoperation
lifeovertimeifthesystemisnotdesignedtodraincondensation.Itisrecommendedto
mounttheOutdoorCoolerinaverticalorientation,socondensationrunsoffthecold
side heat exchanger. If the enclosure cannot accommodate this, then the Outdoor Cool-
ershouldbeinstalledataminimum15degreeangleinhorizontalorientationtoallow
forcondensationtorunoffthecoldsideheatexchanger.
The Outdoor Cooler must be protected from vandalism or external forces that may
bump up against unit and cause damage.
Mounting & Hardware
The enclosure should be sealed from the outside environment by maintaining good
compression between the Outdoor Cooler and cabinet wall. The Outdoor Coolers are
designed to be through mount, so a cut out on the enclosure wall will be required to
accommodatethecoldsideheatexchanger.Referencethebelowdiagramformounting
holelocationsandcoldsideheatexchangerdimensions.Thecutoutshouldbe2.5mm’s
largerthanthecoldsideheatexchanger.Eightmountingholesareavailabletofasten
theOutdoorCoolerunittocabinetwall.Themountingholesaredesignedtoaccom-
modate M5 machine hardware as shown in diagram. External tooth lock washers are
recommendedtopreventOutdoorCoolerfromlooseningovertime.
280 330 96 \/ + ‘“\HWH\1‘\H\HH\\HH\\H\HHHHHHHHHW“ 05.5 (8x) / 4k ’ “‘HHHHH\“\\HHW\H\HHHHHH‘WHHW “ H— 316 306
THR-UM-AA-480-XX_03157www.lairdtech.com
306
316
96
330
Φ5.5 (8x)
280
280 
59.3122.1 43.9
306
3
Sealing gasket
Sealing gasket
330
303
171.4
57.6
306
Tooth washer
Nut
Cabinet wall
Machine screw
Flat washer
TE-unit





comma nun Imwnx mu "mam am TERMINM sLCItK WITN I magnum 2w TEM BLOCK 24v mm BLOCK INT mu- I luv m» I m m. I m W I my "IA 24v 1:»: BLOCK 24v mm mm mm I I "IA I I I I
THR-UM-AA-480-XX_03158www.lairdtech.com
Schematic
Outdoor Coolers come with a durable simple to use cage clamp. Wires should be
strippedback6mm’sinlengthandinsertedintoconnector.Connectorcanaccommo-
datewiresizesof12to28AWG.ForinputpowertoTEM16AWGstrandedcopper
wire is recommended. For input power to fans 18 AWG stranded copper wire is
recommended.
InternalschematicofOutdoorCoolerUnit.(24Voltschematicshown)







 


 
 

















1. Connect external fuse in line with input power connector to protect input power
linesfromshorting.
2.Inputvoltagemustnotexceedratingonlabelofunit.Maximumripplecurrent
should not exceed three percent of nominal value.
THR-UM-AA-480-XX_03159www.lairdtech.com
Serviceability
NospecialmaintenanceisrequiredwhenusingLairdOutdoorCoolers.Forcontinued
optimalperformanceandextendedlifeoftheunit,itisrecommendedtocleanthe
(internal/external)heatsinksandfansperiodicallyastheywillaccumulatedustfrom
outsidecontaminantsovertime.IfaunitisnotperformingproperlyconsultwithLaird.
Warranty
Laird Outdoor Coolers are manufactured in an ISO 9001:2008 facility. Units adhere to
the highest quality standards and are free from defects in material, components, and
workmanship. This warranty covers repair or replacement of product, to be done at a
Lairdfacility,foraperiodoftwo(2)yearsfromdateofshipment.Customerisresponsi-
ble for shipping product to Laird freight prepaid. Laird in turn will return the warranted
producttocustomerfreightprepaid,ifwithinthetimeperiodspecifiedabove.Warranty
coverageisineffectwhenthefollowingoperatingconditionsarecontinuouslysatisfied:
• AmbientTemperatureRangewithin-40°Cto55°C.
• LineVoltagevariationwithinplusorminus10%ofnameplaterating.
Inaddition,thefollowingcriteriamustbemet:
• Electricalinstallationandgroundingmustcomplywithlocalelectricalandsafety
codes.
Outdoor Cooler must be used in the environment for which it is designed.
• Customercannotabuseormishandletheproductinanyway.Anymodificationsto
the original unit will also void warranty.
• CompliancetoUsersManualoranyotherinstructionalguideprovidedbyLairdfor
the product.
This warranty does not cover the following:
• Applicationswhereproductisbeingmisapplied.Thisincludesinappropriate
selectionofOutdoorCoolerfortheenvironmentandconditionsinwhichitistobe
used.
• Damagescausedbyshippingcarrieroranyotheraccidentafterproducthasleft
Laird. Shipping claims are the responsibility of the customer and are to be com-
pletedinatimelymanner.
• Reimbursementoflaborforinstallationorremovalofwarrantedproduct,orfor
partsandlaborresultingfromrepairsperformedbyanyothersourcebesidesLaird.
This is the complete warranty and is in lieu of any other warranty expressed or implied,
includingbutnotlimitedtoanyimpliedwarrantyofmerchantabilityorfitnessfora
particularpurpose.Lairdwillinnowaybeliableforincidentalorconsequentialdamage
whatsoeverorforanyotherclaimsbythecustomerfordamagesinconnectionwith
Laird products, even if advised in advance of the possibility of such damage.
THR-UM-AA-480-XX_031510 www.lairdtech.com
Return Procedure
AllreturnsmustbeassignedaNon-ConformanceMaterialReturnAuthorizationnumber
(NCMR#)inadvance.ReturnsreceivedwithoutRMA#mayberefused.Intheevent
that a return is required, the Customer should call Laird Customer Service Department
atUSA:+1.919.597.7300,Europe:+46.31.420530,Asia:+86.755.2714.1166orsendan
emailtoorder.gothenburg@lairdtech.com.TheCustomerwillbeaskedtofilloutan
NCMR form so that NCMR number can be issued. All returns must be securely packed
to prevent shipping damage and must be clearly marked with the NCMR number on the
box. Consignor shall pay freight charges on all returns.
La'rd) SmarKTemno‘ogy Delweved '
THR-UM-AA-480-XX_0315
Any information furnished by Laird and its agents is believed to be accurate and reliable. All specifications are subject to change without notice. Responsibility for the use and
application of Laird materials rests with the end user, since Laird and its agents cannot be aware of all potential uses. Laird makes no warranties as to the fitness, merchantability
or suitability of any Laird materials or products for any specific or general uses. Laird, Laird Technologies, Inc or any of its affiliates or agents shall not be liable for incidental or
consequential damages of any kind. All Laird products are sold pursuant to the Laird Terms and Conditions of sale in effect from time to time, a copy of which will be furnished
upon request. © Copyright 2015 Laird Technologies, Inc. All Rights Reserved. Laird, Laird Technologies, the Laird Logo, and other marks are trademarks or registered trademarks
of Laird Technologies, Inc. or an affiliate company thereof. Other product or service names may be the property of third parties. Nothing herein provides a license under any Laird
or any third party intellectual property rights.
Americas:+1.919.597.7300
Europe:+46.31.420530
Asia:+86.755.2714.1166
www.lairdtech.com
order.gothenburg@lairdtech.com